How to use the wire size calculator
- Enter the load current and voltage, and choose DC, single-phase or three-phase AC.
- Enter the one-way distance from the panel or source to the load, and the voltage drop you'll accept (3% is a common target).
- For copper, pick the ampacity column and tick "continuous load" if it runs for 3 hours or more. The calculator picks the larger of the size needed for the current and the size needed for voltage drop.
Formulas
Voltage drop (three-phase) = √3 × I × R × L (R in Ω per foot, L = one-way feet)
AWG diameter = 0.127 mm × 92^((36 − n) ÷ 39) (1/0 = 0, 2/0 = −1, 3/0 = −2, 4/0 = −3)
Required size = larger of (ampacity ≥ current × 1.25 if continuous) and (drop ≤ limit)
Worked examples
| Circuit | Ampacity needs | Voltage drop needs (≤3%) | Use |
|---|---|---|---|
| 20 A, 120 V, 100 ft, copper | 12 AWG | 8 AWG (2.55%; 12 AWG would drop 6.4%) | 8 AWG |
| 30 A, 240 V, 50 ft, copper | 10 AWG | 10 AWG (1.52%) | 10 AWG |
| 16 A continuous, 120 V, 25 ft, copper | 12 AWG (16 × 1.25 = 20 A) | 14 AWG | 12 AWG |
Copper ampacity (NEC Table 310.16)
| AWG | 60 °C | 75 °C | AWG | 60 °C | 75 °C |
|---|---|---|---|---|---|
| 14* | 15 | 20 | 2 | 95 | 115 |
| 12* | 20 | 25 | 1 | 110 | 130 |
| 10* | 30 | 35 | 1/0 | 125 | 150 |
| 8 | 40 | 50 | 2/0 | 145 | 175 |
| 6 | 55 | 65 | 3/0 | 165 | 200 |
| 4 | 70 | 85 | 4/0 | 195 | 230 |
*NEC 240.4(D) limits overcurrent protection for copper to 15 A on 14 AWG, 20 A on 12 AWG and 30 A on 10 AWG, whatever the table says. Values assume no more than three current-carrying conductors and 30 °C ambient; more conductors or heat require derating.
AWG size chart
| AWG | Diameter | Area | Copper Ω/1000 ft (75 °C) |
|---|---|---|---|
| 14 | 1.628 mm (0.0641 in) | 2.08 mm² (4.1 kcmil) | 3.071 |
| 12 | 2.053 mm (0.0808 in) | 3.31 mm² (6.5 kcmil) | 1.932 |
| 10 | 2.588 mm (0.1019 in) | 5.26 mm² (10.4 kcmil) | 1.215 |
| 8 | 3.264 mm (0.1285 in) | 8.37 mm² (16.5 kcmil) | 0.764 |
| 6 | 4.115 mm (0.1620 in) | 13.30 mm² (26.3 kcmil) | 0.480 |
| 4 | 5.189 mm (0.2043 in) | 21.15 mm² (41.7 kcmil) | 0.302 |
| 3 | 5.827 mm (0.2294 in) | 26.67 mm² (52.6 kcmil) | 0.240 |
| 2 | 6.544 mm (0.2576 in) | 33.63 mm² (66.4 kcmil) | 0.190 |
| 1 | 7.348 mm (0.2893 in) | 42.41 mm² (83.7 kcmil) | 0.151 |
| 1/0 | 8.251 mm (0.3249 in) | 53.48 mm² (105.5 kcmil) | 0.120 |
| 2/0 | 9.266 mm (0.3648 in) | 67.43 mm² (133.1 kcmil) | 0.095 |
| 3/0 | 10.405 mm (0.4096 in) | 85.03 mm² (167.8 kcmil) | 0.075 |
| 4/0 | 11.684 mm (0.4600 in) | 107.22 mm² (211.6 kcmil) | 0.060 |
Resistances are calculated from copper's resistivity for a solid conductor at 75 °C and closely match NEC Chapter 9, Table 8; stranded wire is about 2% higher. Diameters come from the AWG formula; the wire's cross-section is a circle, the same math as the cylinder volume calculator.
Safety tips
- Match the breaker to the wire, never the other way around: a breaker bigger than the wire's rating can let it overheat.
- Low-voltage DC (12 V, 24 V) needs thick wire for any distance: 10 A at 12 V over 20 ft drops 6.4% even on 12 AWG copper.
- Check derating for attics, conduit with many wires and buried runs, and use the right cable type for the location.
Planning estimates only, not electrical design advice. Follow your local electrical code and have work inspected; hire a licensed electrician for mains wiring. Large numbers in physics problems? Try the scientific notation converter. More science calculators.
Sources
Frequently asked questions
What size wire do I need for 20 amps?
For copper building wire, 12 AWG is the usual minimum for a 20-amp circuit: NEC 240.4(D) limits 12 AWG copper to a 20 A breaker and 14 AWG to 15 A. On long runs you may need thicker wire to limit voltage drop: a 20 A, 120 V load 100 feet away needs 8 AWG to stay under 3% drop.
How do you calculate voltage drop?
For DC and single-phase AC: voltage drop = 2 × current × resistance per foot × one-way length. For three-phase, use √3 instead of 2. 12 AWG copper is about 1.93 Ω per 1,000 ft, so 20 A over 100 ft drops 2 × 20 × 0.00193 × 100 = 7.7 V, or 6.4% of 120 V.
What is an acceptable voltage drop?
A common design target is no more than 3% on a branch circuit and 5% total from service to load, which comes from informational notes in the NEC. They're recommendations for efficiency and performance rather than strict rules, but they're widely followed.
What does AWG mean, and why is a smaller number a bigger wire?
AWG is American Wire Gauge. The numbers come from how many drawing steps the wire went through, so a lower number means a thicker wire. Every 3 gauges roughly doubles the cross-sectional area (and halves the resistance); every 6 gauges doubles the diameter.
What is the difference between the 60 °C and 75 °C columns?
NEC Table 310.16 lists how much current a conductor can carry based on its insulation temperature rating. You also have to respect the rating of the terminals it connects to; for circuits of 100 A or less, terminals are often assumed to be 60 °C unless marked otherwise, so the 60 °C column is the safe default.
Can I use aluminum wire?
Aluminum conducts about 61% as well as copper, so it needs to be about two gauge sizes larger for the same resistance. It's common for large feeders and service entrances, but needs connectors and devices rated for aluminum. This calculator sizes aluminum for voltage drop; check its ampacity in the aluminum column of Table 310.16.
Does this replace the electrical code?
No. Real installations also depend on derating for many conductors in a conduit, high ambient temperature, insulation type, local amendments and inspection. Use this as a planning estimate and follow your local code, or hire a licensed electrician.