Work out vapor pressure deficit (VPD) at the leaf from air temperature, humidity and leaf temperature, then compare it with the target for seedlings, vegetative growth or flowering and find the humidity that hits it.

Units
ยฐC
%
ยฐC

Leaf minus air; transpiring leaves are often 1โ€“3 ยฐC cooler

Growth stage

Leaf VPD

0.91 kPa

In the vegetative growth range

Air VPD (no leaf offset)
1.27 kPa
Vegetative growth target
0.8โ€“1.2 kPa
Humidity for that target
51โ€“63% RH
Dew point
16.7 ยฐC
Saturation vapor pressure
3.17 kPa
Actual vapor pressure
1.90 kPa

Stage ranges are general guidelines for many indoor crops; follow crop-specific advice where you have it. Measure leaf temperature with an infrared thermometer for the most accurate leaf VPD.

VPD chart (leaf offset -2 ยฐC)

Temp \ RH40%45%50%55%60%65%70%75%80%
18ยฐC0.990.890.790.680.580.480.370.270.17
20ยฐC1.131.010.890.780.660.540.430.310.19
22ยฐC1.281.151.020.880.750.620.490.360.22
24ยฐC1.451.301.151.000.850.700.560.410.26
26ยฐC1.641.471.301.140.970.800.630.460.29
28ยฐC1.851.661.471.281.090.900.720.530.34
30ยฐC2.081.871.661.451.231.020.810.600.39
32ยฐC2.342.101.871.631.391.150.910.680.44

< 0.4 too humid0.4โ€“0.8 propagation0.8โ€“1.2 vegetative1.2โ€“1.6 flowering> 1.6 too dry

How to use the VPD calculator

  1. Enter the air temperature and relative humidity at canopy height.
  2. Set the leaf temperature offset (leaf minus air). Measure it with an infrared thermometer, or use โˆ’1 to โˆ’3 ยฐC for healthy, transpiring leaves under LEDs.
  3. Choose the growth stage to compare your leaf VPD with its target range and see the humidity that would hit it. The chart shows VPD across common temperatures and humidities.

VPD formulas

SVP(T) = 0.61078 ร— e^(17.27T รท (T + 237.3)) kPa (Tetens, T in ยฐC)
Actual vapor pressure = SVP(air) ร— RH รท 100
Air VPD = SVP(air) โˆ’ actual vapor pressure ยท Leaf VPD = SVP(leaf) โˆ’ actual vapor pressure

Worked example

At 25 ยฐC and 60% RH: SVP = 3.17 kPa and the actual vapor pressure is 1.90 kPa, so air VPD = 1.27 kPa. With leaves 2 ยฐC cooler (23 ยฐC), SVP(leaf) = 2.81 kPa, so leaf VPD = 0.91 kPa, right in the vegetative range. The dew point is about 16.7 ยฐC.

Target VPD by growth stage

StageLeaf VPDWhy
Propagation / seedlings0.4โ€“0.8 kPaSmall roots; humid air limits water loss
Vegetative0.8โ€“1.2 kPaSteady transpiration drives nutrient uptake
Flowering / fruiting1.2โ€“1.6 kPaDrier air lowers mold and rot risk

Tips for controlling VPD

  • Measure at the canopy, not near the floor or the lights.
  • Watch lights-off: when lights go off, temperature drops and humidity jumps, which can cause condensation.
  • Size equipment: dehumidifiers and air conditioners work together; see the BTU calculator for cooling.

For air density effects of temperature and humidity, see the density altitude calculator. Preparing nutrient solutions? The molarity calculator helps. More science calculators.

Sources

Frequently asked questions

What is VPD?

Vapor pressure deficit is the difference between how much water vapor the air could hold at saturation and how much it actually holds, in kilopascals (kPa). It drives how fast plants transpire: low VPD means humid, slow-drying air; high VPD means dry air that pulls water out of leaves quickly.

How do you calculate VPD?

Find the saturation vapor pressure with the Tetens equation, SVP = 0.61078 ร— e^(17.27T รท (T + 237.3)) kPa, with T in ยฐC. Air VPD = SVP(air) ร— (1 โˆ’ RH/100). Leaf VPD = SVP(leaf temperature) โˆ’ SVP(air) ร— RH/100.

What is a good VPD for plants?

A widely used guide is about 0.4โ€“0.8 kPa for propagation and seedlings, 0.8โ€“1.2 kPa for vegetative growth and 1.2โ€“1.6 kPa for flowering and fruiting. Below about 0.4 kPa the air is so humid that disease risk rises; above about 1.6 kPa many plants close their stomata and slow down.

Why use leaf temperature instead of air temperature?

The leaf surface is where water evaporates, and transpiring leaves are usually a little cooler than the air, often 1โ€“3 ยฐC. At 25 ยฐC and 60% RH, air VPD is 1.27 kPa, but with leaves 2 ยฐC cooler the leaf VPD is about 0.91 kPa.

How do I raise or lower VPD?

To lower VPD, raise humidity (humidifier, less extraction) or lower temperature. To raise VPD, lower humidity (dehumidifier, more air exchange) or raise temperature. Change one thing at a time and give plants time to adjust.

What humidity do I need for a target VPD?

RH = (SVP at leaf temperature โˆ’ target VPD) รท SVP at air temperature ร— 100. At 25 ยฐC with leaves 2 ยฐC cooler, a 1.0 kPa target needs about 57% RH. The calculator shows the RH range for the selected growth stage.