Watts to Amps Calculator

Amps = watts รท volts for DC and resistive loads, so 1,500 W at 120 V draws 12.5 A. For AC motors and three-phase power, power factor and โˆš3 come in. Convert either way for any circuit.

Convert
Circuit
V

1 for heaters and incandescent bulbs; lower for motors

I = P รท (PF ร— V)

Current

12.5 A

1,500 W at 120 V, power factor 1

Apparent power
1,500 VA (1.5 kVA)
Circuit rating for a continuous load
at least 15.63 A
Same load atCurrent
110 V13.64 A
120 V12.5 A
208 V7.21 A
220 V6.82 A
230 V6.52 A
240 V6.25 A

For continuous loads (3 hours or more), the U.S. National Electrical Code generally limits circuits to 80% of the breaker rating. Motors draw extra current at start-up. Have a licensed electrician size circuits.

How to use the watts to amps calculator

  1. Choose watts โ†’ amps or amps โ†’ watts.
  2. Pick the circuit: DC (batteries, solar, cars), single-phase AC (most homes) or three-phase AC (commercial and industrial).
  3. Enter the voltage and, for AC, the power factor from the nameplate (use 1 for heaters and other resistive loads).

Watts and amps formulas

CircuitAmpsWatts
DCI = P รท VP = V ร— I
AC single-phaseI = P รท (PF ร— V)P = PF ร— V ร— I
AC three-phase (line to line)I = P รท (โˆš3 ร— PF ร— V)P = โˆš3 ร— PF ร— V ร— I
AC three-phase (line to neutral)I = P รท (3 ร— PF ร— V)P = 3 ร— PF ร— V ร— I

Worked examples

  • 1,500 W heater at 120 V (PF 1): 1,500 รท 120 = 12.5 A.
  • 1,500 W load at 230 V, PF 0.9: 1,500 รท (0.9 ร— 230) = 7.25 A.
  • 15 kW three-phase motor at 400 V, PF 0.9: 15,000 รท (1.732 ร— 400 ร— 0.9) = 24.06 A.
  • 10 A at 120 V: 10 ร— 120 = 1,200 W.

Amps for common wattages at 120 V and 240 V (PF 1)

Watts120 V240 V
100 W0.83 A0.42 A
500 W4.17 A2.08 A
1,000 W8.33 A4.17 A
1,500 W12.5 A6.25 A
2,000 W16.67 A8.33 A
3,000 W25 A12.5 A
5,000 W41.67 A20.83 A

For resistance and the full Ohm's law set, use the Ohm's law calculator; to choose cable for the current, the wire size calculator; and to size an air conditioner, the BTU calculator. More science and engineering calculators.

Sources

Frequently asked questions

How do you convert watts to amps?

For DC: amps = watts รท volts. For single-phase AC: amps = watts รท (power factor ร— volts). For three-phase AC with line-to-line voltage: amps = watts รท (โˆš3 ร— power factor ร— volts).

How many amps is 1,500 watts?

At 120 V with a power factor of 1 (a space heater, for example), 1,500 W draws 1,500 รท 120 = 12.5 A. At 240 V it draws 6.25 A, and at 230 V with a 0.9 power factor about 7.25 A.

How do you convert amps to watts?

Watts = amps ร— volts for DC, amps ร— volts ร— power factor for single-phase AC, and โˆš3 ร— amps ร— volts ร— power factor for three-phase AC (line-to-line voltage). 10 A at 120 V is 1,200 W for a resistive load.

What is power factor?

The ratio of real power (watts) to apparent power (volt-amperes). Resistive loads such as heaters, kettles and incandescent bulbs have a power factor of about 1. Motors, compressors and some electronics are lower, so they draw more current for the same wattage. The equipment nameplate often lists it.

How do I calculate three-phase amps?

Divide the power by โˆš3 ร— voltage ร— power factor when you know the line-to-line voltage. A 15 kW load at 400 V and 0.9 power factor draws 15,000 รท (1.732 ร— 400 ร— 0.9) โ‰ˆ 24.06 A per phase.

What size breaker do I need for my load?

For continuous loads, U.S. practice is to keep the load at no more than 80% of the breaker rating, so divide the amps by 0.8: a 10 A continuous load needs at least a 12.5 A circuit, in practice a 15 A breaker. Wire size must also match; have an electrician confirm.