How to use the watts to amps calculator
- Choose watts โ amps or amps โ watts.
- Pick the circuit: DC (batteries, solar, cars), single-phase AC (most homes) or three-phase AC (commercial and industrial).
- Enter the voltage and, for AC, the power factor from the nameplate (use 1 for heaters and other resistive loads).
Watts and amps formulas
| Circuit | Amps | Watts |
|---|---|---|
| DC | I = P รท V | P = V ร I |
| AC single-phase | I = P รท (PF ร V) | P = PF ร V ร I |
| AC three-phase (line to line) | I = P รท (โ3 ร PF ร V) | P = โ3 ร PF ร V ร I |
| AC three-phase (line to neutral) | I = P รท (3 ร PF ร V) | P = 3 ร PF ร V ร I |
Worked examples
- 1,500 W heater at 120 V (PF 1): 1,500 รท 120 = 12.5 A.
- 1,500 W load at 230 V, PF 0.9: 1,500 รท (0.9 ร 230) = 7.25 A.
- 15 kW three-phase motor at 400 V, PF 0.9: 15,000 รท (1.732 ร 400 ร 0.9) = 24.06 A.
- 10 A at 120 V: 10 ร 120 = 1,200 W.
Amps for common wattages at 120 V and 240 V (PF 1)
| Watts | 120 V | 240 V |
|---|---|---|
| 100 W | 0.83 A | 0.42 A |
| 500 W | 4.17 A | 2.08 A |
| 1,000 W | 8.33 A | 4.17 A |
| 1,500 W | 12.5 A | 6.25 A |
| 2,000 W | 16.67 A | 8.33 A |
| 3,000 W | 25 A | 12.5 A |
| 5,000 W | 41.67 A | 20.83 A |
For resistance and the full Ohm's law set, use the Ohm's law calculator; to choose cable for the current, the wire size calculator; and to size an air conditioner, the BTU calculator. More science and engineering calculators.
Sources
Frequently asked questions
How do you convert watts to amps?
For DC: amps = watts รท volts. For single-phase AC: amps = watts รท (power factor ร volts). For three-phase AC with line-to-line voltage: amps = watts รท (โ3 ร power factor ร volts).
How many amps is 1,500 watts?
At 120 V with a power factor of 1 (a space heater, for example), 1,500 W draws 1,500 รท 120 = 12.5 A. At 240 V it draws 6.25 A, and at 230 V with a 0.9 power factor about 7.25 A.
How do you convert amps to watts?
Watts = amps ร volts for DC, amps ร volts ร power factor for single-phase AC, and โ3 ร amps ร volts ร power factor for three-phase AC (line-to-line voltage). 10 A at 120 V is 1,200 W for a resistive load.
What is power factor?
The ratio of real power (watts) to apparent power (volt-amperes). Resistive loads such as heaters, kettles and incandescent bulbs have a power factor of about 1. Motors, compressors and some electronics are lower, so they draw more current for the same wattage. The equipment nameplate often lists it.
How do I calculate three-phase amps?
Divide the power by โ3 ร voltage ร power factor when you know the line-to-line voltage. A 15 kW load at 400 V and 0.9 power factor draws 15,000 รท (1.732 ร 400 ร 0.9) โ 24.06 A per phase.
What size breaker do I need for my load?
For continuous loads, U.S. practice is to keep the load at no more than 80% of the breaker rating, so divide the amps by 0.8: a 10 A continuous load needs at least a 12.5 A circuit, in practice a 15 A breaker. Wire size must also match; have an electrician confirm.